6.2 Configuring the busbar run layout
SIVACON 8PS - Configuring with LX system
116 Configuration Manual, 10/2011, A5E02194899-02
Vertical busbar run layout between junction unit and end cap, Case 2
● Expansion compensation unit is not required in the topmost sub-run to the end cap.
● Position further expansion compensation units in the centre between the fixed points.
)3
)3
'
//
/
()
L1 Max. permissible sub-length
L Total run length
D Expansion compensation
FP Fixed point (type: LX-BVFP..)
EF End cap
Examples of power distribution with LXA...., (LXC....)
Run length L
[m]
Number of fixed points (FP) Number of expansion
compensation units (D)
≤ 50 (≤ 60) 1 0
≤ 100 (≤ 120) 2 1
≤ 150 (≤ 180) 3 2
≤ 200 (≤ 240) 4 3