Questions and Answers

  • S
    Sharon MartinAug 12, 2025
    What to do if my Sincro HB4 Inverter has no voltage?
    • A
      Angela DavisAug 12, 2025
      If your Sincro Inverter shows no voltage, several issues could be the cause. First, check all connections to ensure they are secure. A faulty AVR could be the problem; check the fuse and consider replacing the AVR. Also, inspect the rectifier bridge. An open stator exciter circuit or a main winding fault could also be responsible; check the stator/rotor windings resistances and insulation. In some cases, the machine may be demagnetized; excite the alternator by applying a 6-12 voltage across the exciter terminals for a second, respecting the polarities while the engine is running.
  • M
    Michael RamirezAug 27, 2025
    What causes high voltage in a Sincro HB4?
    • B
      Brandon TorresAug 27, 2025
      If your Sincro Inverter is producing high voltage, the issue may stem from several causes. Begin by adjusting the voltage with the potentiometer «V» on the AVR to ensure the reference voltage is correctly set. Check the sensing connections to rule out an open circuit. If the problem persists, the AVR may be faulty and require replacement.
  • A
    Adam MathisSep 2, 2025
    How to fix unstable voltage on a Sincro Inverter?
    • D
      David MahoneySep 2, 2025
      If your Sincro Inverter's voltage is unstable, there are a few things you can check. First, make sure the AVR stability is correctly set by checking the correct Dip switches position and adjusting stability with the ST trimmer. Also, check for oscillations in engine speed using a frequency meter. If these steps don't resolve the issue, the AVR may be faulty and need to be replaced.
  • G
    Grace VillegasSep 10, 2025
    Why is my Sincro HB4 Inverter voltage so low?
    • A
      April OrrSep 12, 2025
      If your Sincro Inverter is showing low voltage, try these steps: * Adjust the voltage using the potentiometer «V» on the AVR to set the reference voltage to the desired value. * Check and adjust the under-frequency protection value for the nominal frequency (50Hz or 60Hz). * Verify the engine speed to ensure it is correct, as a low engine speed can cause low voltage. * If these steps don't work, the AVR may be faulty and need replacement.

Sincro HB4 Specifications

General IconGeneral
Output Voltage230 Vac
Power4000W
Rated Power4 kW
Frequency50 Hz / 60 Hz
ProtectionOverload, short circuit, overvoltage
PhasesSingle phase