EasyManua.ls Logo

Sincro HB4 - RD2 AVR Settings

Sincro HB4
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.4.5 RD2 AVR
TheAVR controls the generator voltage. TheAVR is
used to keep a constant voltage when the load and
machineparametersvary.
TheAVR requires a so-called sensing connection; a
powersupplyfromaspecificcircuit(AUX);anoutputto
therotor(+/-).
In case of unbalanced or distorted load, voltage
regulationaccuracycouldbereduced.
Afrequencycontrolprogressivelyreducesthegenerator
excitationwhenthedriveenginespeeddropsbelowa
pre-set,adjustablethresholdpreventingover-excitation
atlowoperatingspeedsandabatingtheloadengage
effectsontheengine.
In conclusion the regulator reaction time can be
modulatedtoeliminateanyvoltageinstabilitythatmay
arise.
The output voltage can be changed by adjusting
potentiometerV”.Runthegeneratingsettoitsnominal
speedandturnuntil the required voltage is obtained.
If a small variation in speed causes a change in
voltage,thentheunderspeedprotectionshouldfirstbe
calibrated.
Thevoltagesensingjumpershouldbeconnected:
• toterminals“115”ifconnectedtoavoltagebetween
100 and 130V
• toterminals230”ifconnectedtoavoltagebetween
185 and 245V.
• toterminals400”ifconnectedtoavoltagebetween
340 and 460V.
• toterminals480”ifconnectedtoavoltagebetween
440 and 520V.
Stability adjustment: if onload voltage fluctuations
are experienced adjust potentiometer ST”, which
modulatesthereactiontimeoftheregulatortoexternal
inputs, thereby eliminating any instability in the
alternator-loadsystem.
IftheadjustmentviapotentiometerSTdoesnotprove
tobesufficient,ispossiblealsoto use the dip-switch
ST+/ST:movingittotheONposition(ST+)stability
increases.
Setting of the under speed protection at 50 (60)
Hz:startuprotationofthegeneratingsetadjustingitto
obtainafrequencyof46(56)Hz.TurntrimmerUF”until
thevoltagebeginstodrop.Restorenominalspeed.
Remote voltages adjustment :wirethepotentiometer
(5kOhm, 3W)totheshortedterminalsEXT POT.Run
thegeneratingsettoitsnominalspeedandadjustthe
externalpotentiometerandeventuallyalsothetrimmer
“V”toobtaintherequiredvoltage.
Remote voltages adjustment :
1) with potentiometer: TurnONthedip-switchEXT-
POT (and make sure the dip switches EXT-VOLT is
turnedOFF).
Wirethepotentiometer(5kOhm, 3W)totheterminals
EXT POT.Runthegeneratingsettoitsnominalspeed
andadjusttheexternalpotentiometerandtrimmer“V”to
obtainthedesiredvoltage.Theexternalpotentiometer
hastheeffectofincreasingthevoltagevaluesetbythe
“V”trimmer.
2) Connection with controller or cosf regulator: Turn
ONthedip-switchEXT-VOLT(andmakesurethedip
switchesEXT-POTisturnedOFF).TheAVRregulator
accepts voltage analogic input (0-10VDC, observe
polarityshowninfigure)forremotevoltageadjustment.
Tosetthesystem,followthisprocedure:
- Decrease the voltage by turning the “V” trimmer
counter-clockwise;
-Applyhalfthecontrolvoltageatthe“EXTpot”terminals
(5VDC);
- Act on the “V” trimmer to bring the voltage to the
nominalvalue;
in this way, the external controller can increase or
decreasetheoutputvoltage.
Incasetheremotevoltageadjustmentisnotused,turn
OFF the dip-switches EXT-POT and EXT-VOLT. Pay
attentionnottoturnONboththedip-switches.
If the voltage is set any higher than its
maximum limit the generator may be
damaged.
WARNING!
If the under speed is set at too low
a frequency, the generator may be
damaged.Ontheotherhand,toohigha
frequency can cause voltage drops with
highloads.
WARNING!
Frequency
Dip-switch
Voltage
Dip-switch
Phase
Dip-switch
Voltage
increasing
Voltage
decreasing
Underfrequency
protection limit
increasing
Underfrequency
protection limit
decreasing
Stability
decreasing
Stability
increasing
Connection with controller,
Observe polarity:
V
CW
CCW
Voltage
Increase
Voltage
Decrease
CW
CCW
Stability
Decrease
Stability
Increase
ST
CW
CCW
Corner
Frequency
Increase
UF
Corner
Frequency
Decrease
L
N
+
-
C BA
V ST
UF
Off
On
Off
On
0V (-)
0-10V (+)
Polarity of EXT. Voltage
Off
On
V
CW
CCW
Voltage
Increase
Voltage
Decrease
CW
CCW
Stability
Decrease
Stability
Increase
ST
CW
CCW
Corner
Frequency
Increase
UF
Corner
Frequency
Decrease
L
N
+
-
C BA
V ST
UF
Off
On
Off
On
0V (-)
0-10V (+)
Polarity of EXT. Voltage
Off
On
V
CW
CCW
Voltage
Increase
Voltage
Decrease
CW
CCW
Stability
Decrease
Stability
Increase
ST
CW
CCW
Corner
Frequency
Increase
UF
Corner
Frequency
Decrease
L
N
+
-
C BA
V ST
UF
Off
On
Off
On
0V (-)
0-10V (+)
Polarity of EXT. Voltage
Off
On
V
CW
CCW
Voltage
Increase
Voltage
Decrease
CW
CCW
Stability
Decrease
Stability
Increase
ST
CW
CCW
Corner
Frequency
Increase
UF
Corner
Frequency
Decrease
L
N
+
-
C BA
V ST
UF
Off
On
Off
On
0V (-)
0-10V (+)
Polarity of EXT. Voltage
Off
On
0V (-)
0-10V (+)
Off
On
24
ITALIANOENGLISHFRANÇAISDEUTSCHESPAÑOL

Table of Contents

Related product manuals