Sincro HB4 - Troubleshooting

Sincro HB4
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FAULT POSSIBLE REASON CHECK / REMEDY
NO VOLTAGE
FaultyAVR
• checkthefuse
• replacetheAVR
Faultyrectierbridgeand/orsurgesuppres-
sor
• checkrectierbridge
Faultystatorexciter • checkifthestatorexcitercircuitisopen
Mainwindingfault
• checkstator/rotorwindingsresistances
• checkstator/rotorwindingsinsulation
resistance
Demagnetizedmachine
• excitethealternatorbyapplyinga6-12
voltageacrosstheexciterterminalsfora
second,respectingthepolarities.(Engine
isrunning)
Brokenconnections • checkallconnections
LOW VOLTAGE
Referencevoltageisnotsetatdesiredvalue
• adjustvoltagewithpotentiometer«V»on
theAVR;
Under-frequencyprotectonnotproperly
adjusted
• check/adjust,thevalueofunder-frequen-
cyprotectionfor50Hz(60Hz)nominal
frequency.
Enginespeedlow
• checktheenginespeed(voltagefrequen-
cy)
FaultyAVR • replacetheAVR
HIGH VOLTAGE
Referencevoltageisnotsetatdesiredvalue
• adjustvoltagewithpotentiometer«V»on
theAVR
Sensingconnectionopencircuit • checkthesensingconnections
FaultyAVR • replacetheAVR
UNSTABLE
VOLTAGE
AVRstabilityincorrectlyset
• checkthecorrectDipswitchesposition,
adjuststabilitywithSTtrimmer
Enginespeedunstable
• checkwiththefrequencymeterifthere
areoscillationsinenginespeed
FaultyAVR • replacetheAVR
FormorequestionscontacttheSincroAfterSalesService.