INTEGRATION WITH SKF @PTITUDE OBSERVER
IMx-1 system configuration
SKF Enlight Collect IMx-1 System
User Manual
Revision F
37 (101)
Gateway has a drop-down list that allows the selection of any gateway that exists in
the system, or ‘<None>’. Note also that whilst gateways can be associated with
multiple machines, multiple sensors on a machine can only connect to the same,
single gateway. In addition, whilst a machine has a commissioned sensor, it is not
possible to change to another gateway or select ‘<None>’.
Storage condition allows the user to configure the time when measurement
acquisition should be performed.
Measurements schedule is used for selection of the active time period.
Trend measurements can be selected on one or several days of the week. It
contains two settings: measurement interval and Interval alarm.
With options forEvery 1 hour, Every 2 hours’, ‘Every 3 hours, Every 4 hours’,
Every 8 hours, ‘Every 12 hoursand ‘Every 24 hours (default).
Dynamic measurements can also be selected on one or several days of the week.
Measurement intervals and Interval alarm have same options as wellEvery 1
hour, Every 2 hours’, ‘Every 3 hours, Every 4 hours, Every 8 hours, ‘Every 12
hours’ and ‘Every 24 hours (default).
When selecting the above intervals consider the following rules:
Trend measurement in alarm interval (>=) greater than or equal to Trend
measurement interval
Dynamic measurement interval (>=) greater than or equal to Trend
measurement interval
Dynamic measurement (>=) interval greater than or equal to Dynamic alarm
interval and (>=) greater than or equal to Trend measurement alarm interval
In the example above,
Figure 23:
Trend measurement interval will measure on:
Monday, Tuesday, Wednesday, Thursday, Friday, Saturday.
With Active time period over-night from 13:30 to 04:00, Every 4 hours.
[13:30, 17:30, 21:30, 01:30]
If the measurement starts on Saturday, all measurements planed after midnight
(00.00) will execute on Monday, although it is not marked in the user interface.
If the measurement starts on Monday, the last measurement at 01:30 will not execute
because Sunday is not marked in the user interface.
Trend measurement interval alarm will measure on:
Monday, Tuesday, Wednesday, Thursday, Friday, Saturday.
With Active time period over-night from 13:30 to 04:00, Every 2 hours.
[13:30, 15:30, 17:30, 19:30, 21:30, 23:30, 01:30, 03:30]
Dynamic measurement interval will measure on:
Tuesday and Friday. At 13:30, Every 24 hours.

Table of Contents