EasyManua.ls Logo

socomec ISOM Digiware - TR Split-Core Current Sensors

socomec ISOM Digiware
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22 EN
ISOM DIGIWARE - 546780C - SOCOMEC
4.2.4. TR split-core current sensors
The TR split-core current sensors are used to set up measurement points in a new or existing installation without
interfering with its cabling. Thanks to the specic link, they are recognised by the DIRIS B and the overall accuracy of
the measurement chain is guaranteed.
4.2.4.1. Range
Four models are available from 25A to 600A to analyse several types of loads.
TR-10 / iTR-10 TR-14 / iTR-14 TR-21 / iTR-21 TR-32 / iTR-32
Cable passage
diameter
Ø 10mm Ø 14mm Ø 21mm Ø 32mm
Nominal current
range In
25 - 63 A 40 - 160 A 63 - 250 A 160 - 600 A
Recommended
cable section
6 mm² (iTR-10) 10 mm² (iTR-14) 50 mm² (iTR-21) 50 mm² (iTR-32)
Maximum l
75.6A 192A 300A 720A
Part number
4829 0555 / 4829 0655 4829 0556 / 4829 0656 4829 0557 / 4829 0657 4829 0558 / 4829 0658
4.2.4.2. Dimensions
D
B C
A
E
Dimensions in/mm
TR-10 / i TR-10 TR-14 / i TR-14 TR-21 / iTR-21 TR-32 / iTR-32
A
1.74
44
2.63
67
2.56
65
3.38
86
B
1.02
26
1.14
29
1.45
37
2.08
53
C
1.10
28
1.10
28
1.69
43
1.85
47
D
-
0.55
14
0.82
21
1.26
32
E
-
0.59
15
0.90
23
1.30
33
Diameter
0.39
10
0.55
14
0.82
21
1.26
32

Table of Contents