ISOM DIGIWARE - 546780C - SOCOMEC
2.2. Risk of damaging the unit
To ensure that the unit operates correctly, make sure that:
The unit is correctly installed.
The auxiliary power supply voltage indicated on the device: 24 VDC ± 10%.
Use a 230VAC/24VDC SOCOMEC power supply (4829 0120) or use a 1A gG 24VDC fuse.
The 24VDC power supply should be a SELV (safety extra-low voltage).
The network frequency indicated on the device: 50 to 460 Hz.
There is a maximum voltage at the voltage input terminals of 480 VAC phase/phase or 480 VAC phase/neutral or
480 VDC.
Always connect ΔIP, TE, TR or TF current sensors using the recommended connection cables and observing the
maximum prescribed currents.
Only use RJ45 SOCOMEC cables to interconnect the modules via the Digiware bus.
During specic checks, disconnect the devices from the network before attempting to insulate or carry out
dielectric testing.
The devices are designed for indoor use.
If the ambient temperature exceeds +50°C, the minimum temperature of the copper conductors to connect to
terminals should be +85°C.
Failure to respect these precautions could cause damage to the unit or cause an electrical shock.
2.3. Responsibility
Assembly, connection and use must be carried out in accordance with the installation standards currently in force.
The unit must be installed in accordance with the rules given in this manual.
Failure to observe the rules for installing this unit may compromise the device's intrinsic safety.
The unit must be positioned within an installation which complies with the standards currently in force.
Any cable which needs to be replaced may only be replaced with a cable with the correct rating.