75EN
ISOM DIGIWARE - 546780C - SOCOMEC
12.1.6. Environmental specications
Standard model
Ambient operating temperature
-10 to +55°C (IEC 60068-2-1 / IEC 60068-2-2)
Storage temperature
-40 to +70°C (IEC 60068-2-1 / IEC 60068-2-2)
Operating humidity
55°C / 90% RH (IEC 60068-2-30)
Operating altitude
< 2000 m
Vibration 2 Hz to 13.2 Hz – amplitude ± 1 mm (IEC 60068-2-6)
13.2 Hz to 100 Hz – acceleration ± 0.7g (IEC 60068-2-6)
Impact resistance IK08 (5J) front panel
IK06 (1J) other panels
10 g / 11 ms, 3 pulses (IEC 60068-2-27)
PEP ecopassport - ISO 14025 ISOM Digiware: SOCO-00009-V01.01.
Reinforced model "t"
Operating temperature -10°C to +70°C (IEC 60068-2-1 / IEC 60068-2-2)
Storage temperature -40°C to +85°C (IEC 60068-2-1 / IEC 60068-2-2)
Operating humidity 55°C / 97% RH (IEC 60068-2-30)
Operating altitude < 2000 m
Vibration 2.0 Hz to 25.0 Hz – amplitude ± 1.6 mm (IEC 60068-2-6)
25.0 Hz to 100 Hz – acceleration ± 4g (IEC 60068-2-6)
3Hz to 8.7Hz- amplitude ± 10 mm (IEC 60068-2-6)
8.7Hz to 150Hz – acceleration ± 3 g (IEC 60068-2-6)
Impact resistance IK08 (5J) front panel
IK06 (1J) other panels
10 g / 11 ms, 3 pulses (IEC 60068-2-27)
30 g / 18 ms, 3 pulses (IEC 60068-2-27)
40 g / 6 ms, 3 pulses (IEC 60068-2-27)
PEP ecopassport – ISO 14025 ISOM Digiware: SOCO-00009-V01.01.