72 EN
ISOM DIGIWARE - 546780C - SOCOMEC
12. SPECIFICATIONS
12.1. Specications ISOM Digiware L-60, F-60 and T-15
12.1.1. Mechanical specications
Casing type L-60, F-60:
DIN-rail mounting module and base
T-15:
Only is mounted directly on the core balance transformer, DIN rail or board
with Rilsan®
Casing protection index
IP20
Front panel protection index
IP40 on the nose in modular assembly
Material and flammability class of housing
Polycarbonate UL94-V0
Weights ISOM Digiware L-60 / F-60 / T-15 373 g / 103 g / 47 g
12.1.2. Electrical characteristics
DIRIS Digiware C-31
P15 power supply
Specifications 230 VAC / 24 VDC – 0.63A – 15W
Modular format – Dimensions (H x W): 90 x 25 mm Removable screw terminal block, 2 positions, stranded or solid 0.2-
2.5mm² cable
Monitored IT network ISOM Digiware L-60
AC or combined AC/DC L-60: ≤ 480VAC L/L‘ or L/N
L-60h: ≤ 250 VAC
CAT III
AC frequency
50 - 460 Hz
DC
L-60: ≤ 480 VDC
Power consumption L-60: 2.3 W
F-60: 0.8 W
12.1.3. Measurement characteristics
Measurement accuracy
Accuracy L-60 / L-60h:
in accordance with IEC 61557-8
F-60 / T-15:
In accordance with IEC 61557-9 with ΔIPR, WR and TFR
In accordance with IEC 61557-12 classification PMD DD with TE, TR, TF
with U-xx
ISOM Digiware L-60 performance
Specific response value R
an
L-60:
ALARM1: 500 Ω – 1MΩ
ALARM2: 500 Ω – 1MΩ
L-60h:
ALARM1: 50 kΩ – 500 kΩ
ALARM2: 50 kΩ – 500 kΩ
Max. leakage capacity Ce
300 µF, according to profile
Incertitude of specific response value
+/- 10% according to profile
Response time t
an
For Ce=1µF: typical 4s
See curves § 12.3
Measurement voltage Um L-60: 25, 75 or 120 V according to profile
L-60h: 25 V
Measurement current Im
Max 1 mA
Max. external DC voltage Ufg
552 V