Continuous current - 6 circuits
DC / IMD + FLD
L-60
KE L1
FE
L2
L+
L-
1
F-60
I04 I05 I06
I01 I02 I03
M M M M M M
Note relating to connections:
The Easy Cong software can also be used to select numerous other conguration variants for the types of loads and
associated network voltages. (see section 10.1.2.2.)
6.3.3. Coupled networks
6.3.3.1. Simple coupled networks without fault-locating options
In the case of coupled networks, you must ensure that only one IMD is active. You can do this by setting and using
I/O congurations for the ISOM Digiware L-60 (see section 10.1.2.4 on how to congure I/O in "disconnection"
mode).
Principle diagram:
Digiware Digiware
Exclusion IMD
NOTE: Some applications may require you to manage the positions of general cut-off devices of the 2 transformers,
as part of excluding the IMD.
6.3.3.2. Simple coupled networks with fault-locating options
When using fault location on coupled networks, the operability of the IMD ISOM Digiware L-60 must be guaranteed
so it remains active with the whole set of ISOM Digiware F-60 locating devices.
This management is made possible by the 2 ISOM Digiware systems communicating with one another via an inter-
screen Ethernet communication D-X5.