25EN
ISOM DIGIWARE - 546780C - SOCOMEC
5. INSTALLATION
The following paragraphs describe the installation of ISOMDigiware and associated sensors.
5.1. Recommendations and safety
Refer to the safety instructions (section "2) Hazards and Warnings", page 5)
5.2. Installing ISOM Digiware units
5.2.1. ISOM Digiware L-60, F-60, T-15 – mounted on DIN rail
L
1
2
1.38 in
35 mm
0.29 or 0.59 in
7.5 or 15mm
PLEASE NOTE:
When the ISOM T-15 adapter is mounted on DIN rail, do not x the core balance transformer ΔIP to
the T-15
Make sure the housing (e.g. enclosure) is large enough to take the ISOM Digiware L-60 (enough
thermal ventilation around the device)
Make sure that the DIN rail is earthed
Do not install the ISOM T-15 or ISOM Digiware F-60 close to or touching any live parts, or close to
breakers or other equipment carrying dangerous voltage (does not apply to ISOM Digiware L-60)