Power Control Status
ThisscreenisdisplayedonlywhenPowerControlisenabled(availablefromcommunicationboard(CPU)
firmwareversion2.7xx/3.7xxandlater).
P W R C T R L : R E M O T E
P W R L i m i t : 1 0 . 0 4 k W
C o s P h i : 0 . 9
P o w e r P r o d : 7 0 0 0 W
l PWR CTRL:Thepowercontrolstatus:
o
REMOTE-CommunicationwiththeRRCRorsmartenergymanagerisconfirmed/validated.
o
LOCAL-Thepoweriscontrolledlocally(e.g.byafixedlimit),orthisinverterlimitsthePVpower
productiontoitsrelativeportionofthefeed-inpowerlimit,asaresultofdisconnected
communicationwiththesmartenergymanager.Ifthisstatusappears,checkthecommunication
tothesmartenergymanagerorthecommunicationtothemeter.
l PWR Limit:Theinvertermaximumoutputpowersetbyoneofthepowerlimitingoptions:
o
RRCR
o
Smartenergymanager(Feed-inlimitation)
o
P(f)
o
P(U)
o
Q(U)
l Cos Phi:Theratiobetweenactivetoreactivepower
l Power Prod:Thepowerproducedbytheinverter
Formoreinformation,refertothePowerControlApplicationNote,availableonthe
SolarEdgewebsiteathttp://www.solaredge.us/files/pdfs/application_note_power_
control_configuration.pdf.
Battery Status
Thisscreenisdisplayedonlywhenthebatteryisconfigured,andshowsthebattery
identificationinformation,itschargingstatusandpower,andtheoperatingmode.
B S N : X X X X X X X X X I D : 2 4
S O E : 8 9 % W W W W P W R : 2 W
T o t a l : < x > W h
S t a t e : C h a r g i n g
l BSN:Batteryserialnumber
l ID:Batteryidentification-shouldbe24assetupabove
l SOE:StateofEnergy-thebatterycapacitypercentage(calculatedasAvailableEnergy\Max.Energy)
l PWR:Thechargingordischargingpower(inWatts)accordingtothebatterystate(seebelow)
l Total:ThetotaldischargedenergyinWatt/hour
l State:Thebatterystatus:Charging/Discharging,Idle,Init(pre-heating)orFault<errorcode>.
Chapter 7: User Interface
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
67