StorEdge-related Errors Codes
ThissectiondescribestheerrormessagesthatarespecifictotheStorEdgesolution.Fortroubleshooting
errorsthatarenotlistedbelow,contactSolarEdgesupport.ForthegeneralSolarEdgetroubleshooting
refertothecodesintheprevioussection.
Error code
LCD message Cause and Troubleshooting
CPU v3.18
and below
CPU v3.19
and above
178 3x6D Internal RGM Error Check the CTs connections and direction.
179, 180 2xB3, 2xB4
Backup Consumption
Too High
Inverter production stopped due to backed-up loads’
consumption exceeding product rating.
Shutdown non-essential loads to reduce power
consumption.
181 2xB5
Connection Unit
HW Error
Check all the communication cable between the
StorEdge Connection Unit and the digital board in the
inverter.
182 2xB6
Auto-Transformer
Temp. Too High
Inverter production stopped due to auto-transformer
overheating.
Shutdown non-essential loads to reduce the phase
imbalance.
If you use the inverter for on-grid applications only
(without auto-transformer) - move SW2 to the
UP position (ON) (refer to DIP Switch Setup on
page 38).
183 2xB7
Connection Unit
Communication Error
There is a faulty wire connection or an internal error.
o
Check the communication cable between the
StorEdge Connection Unit and the digital board in
the inverter.
o
Check that the StorEdge Connection Unit LEDs
are ON.
184 2xB8
Connection Unit
Temp. Too High
Inverter production stopped due to StorEdge
Connection Unit overheating or due to internal fan
malfunction.
o
Clean the StorEdge Connection Unit fan
o
If the fan is malfunctioning, replace the fan
185 3x6B Meter Comm. Error Refer to Meter Troubleshooting on page 88.
186 3x6B Battery Comm Error
o
Check the wiring to the battery and the battery
DIP switch configuration (refer to Connecting to
the Battery on page 34 and DIP Switch Setup on
page 38.
o
Connecting to the Battery on page 34
o
Check the battery setup in the RS485-Conf screen
(refer to Configuring the RS485 Bus for Battery
and Meter Connection on page 78).
SolarEdge StorEdge Installation Guide MAN-01-000262-1.2
94
StorEdge-related Errors Codes