105
Operation on LCD
====Pu Function====
>Pu Function
> Enable <
====Power Factor====
Response V1
220.0V
Setting PVRT function
PVRT consists of HVRT (High Voltage Ride Through) and LVRT (Low Voltage Ride Through).
With PVRT function, the series inverter can ensure continuous operation without
disconnecting from the grid within a certain range of voltage sudden rise and drop in a
certain time interval.
Enable: Enable the PVRT function
VacUpper: The voltage for high voltage ride through
VacLower: The voltage for low voltage ride through
====FVRT Function====
>Function Control
Enable
====FVRT Function====
>VacUpper
XXX.XV
====FVRT Function====
>VacLower
XXX.XV
Setting Power Limit
Here you can set the rated power by percentage.
The percentage of rated output power is used as the actual output power.
Proportion: Default: 1.00; range: 0.00~1.10
====Power Limit====
Propotion
1.00
Setting DRM function (Applicable to AS4777)
The DRM Function is a demand response method required by the AS4777 standard and is
only applicable to Australia and New Zealand.
The function is enabled by default.
====DRM Function====
>Func Select
Enable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolaX Power X3-ULTRA Series and is the answer not in the manual?

SolaX Power X3-ULTRA Series Specifications

General IconGeneral
BrandSolaX Power
ModelX3-ULTRA Series
CategoryInverter
LanguageEnglish

Related product manuals