Save the measurement to the meter memory using the icon. A detailed description of
memory management is contained in section 5.3.
The last measurement can be recalled using the icon.
U
B
and R
E
are always measured.
The measurement of U
B
, R
E
is always performed with sinusoidal current 0.4 I
n
re-
gardless of the settings concerning waveform and multiplication factor I
n
.
Automatic measurement is interrupted in the following cases:
o the switch was tripped during the measurement of U
B
, R
E
or t
A
at the half value
of I
Δn
,
o the switch did not trip during other component measurements,
o the value of pre-set voltage U
L
has been exceeded,
o voltage was disconnected during one of the component measurements,
o values R
E
and mains voltage did not allow to generate the required current val-
ue for one of component measurements.
The meter automatically skips the measurements impossible to perform, e.g. when
the value of selected current I
Δ
n
and its multiplicity exceed the testing range of the
meter.