MPI-536 USER MANUAL
78
Criteria for assessing the correctness of component results
Parameter
Assessment criterion
Notes
I
A
0.5 I
Δ
n
I
A
≤ 1 I
Δ
n
-
I
A
I
A
0.35 I
Δ
n
I
A
≤ 2 I
Δ
n
for I
Δ
n
= 10 mA
I
A
I
A
0.35 I
Δ
n
I
A
≤ 1.4 I
Δ
n
for other I
Δ
n
I
A
0.5 I
Δ
n
I
A
≤ 2 I
Δ
n
-
I
A
6 mA
3 mA I
A
6 mA
for 6 mA RCD
and RCM
(acc. to IEC 62955 and IEC 62752)
t
A
at 0.5 I
Δ
n
t
A
→ rcd
for all types of RCD
for AC module of RCD
t
A
at 1 I
Δ
n
t
A
≤ 300 ms
for general purpose RCDs
for AC module of RCD
t
A
at 2 I
Δ
n
t
A
≤ 150 ms
for general purpose RCDs
for AC module of RCD
t
A
at 5 I
Δ
n
t
A
≤ 40 ms
for general purpose RCDs
for AC module of RCD
t
A
at 1 I
Δ
n
130 ms t
A
≤ 500 ms
for selective RCDs
t
A
at 2 I
Δ
n
60 ms t
A
≤ 200 ms
for selective RCDs
t
A
at 5 I
Δ
n
50 ms t
A
≤ 150 ms
for selective RCDs
t
A
at 1 I
Δ
n
10 ms t
A
≤ 300 ms
for short-time delay RCDs
t
A
at 2 I
Δ
n
10 ms t
A
≤ 150 ms
for short-time delay RCDs
t
A
at 5 I
Δ
n
10 ms t
A
≤ 40 ms
for short-time delay RCDs
t
A
at 1 I
Δ
n
t
A
10 s
for 6 mA RCD
and RCM
(I
Δ
= 6 mA acc. to IEC 62955 and IEC 62752)
t
A
at 10 I
Δ
n
t
A
≤ 300 ms
for 6 mA RCD
and RCM
(I
Δ
= 60 mA acc. to IEC 62955 and IEC 62752)
t
A
at 33 I
Δ
n
t
A
≤ 100 ms
for 6 mA RCD
and RCM
(I
Δ
= 200 mA acc. to IEC 62955)
t
A
at 50 I
Δ
n
t
A
≤ 40 ms
for 6 mA RCD
and RCM
(I
Δ
= 300 mA acc. to IEC 62752)

Table of Contents