Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-151-
coefficient
0: Enable
1: Disable
Hundreds place: Reserved
0: Reserved
1: Reserved
Control
optimization
setting
0–0x1111
Ones place: Torque command selection
0: Torque reference
1: Torque current reference
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: Whether to enable ASR integral
separation
0: Disable
1: Enable
Thousands place: Reserved
0: Reserved
1: Reserved
Speed loop
differential gain
High-frequency
current loop
proportional
coefficient
Under closed-loop vector control mode (P00.00=3) and
P03.39, the current loop PI parameters are P03.09 and
P03.10; above P03.39, the PI parameters are P03.37
and P03.38.
Setting range of P03.37: 0–65535
Setting range of P03.38: 0–65535
Setting range of P03.39: 0.0–100.0% (relative to max.
frequency)
High-frequency
current loop
integral coefficient
Current loop high-
frequency switch-
over point
Inertia
compensation
enable
Upper limit of
inertia
compensation
torque
Limit the max. inertia compensation torque to prevent
inertia compensation torque from being too large.
Setting range: 0.0–150.0% (rated motor torque)
Inertia
compensation filter
times
Filter times of inertia compensation torque, used to
smooth inertia compensation torque.
Setting range: 0–10
Due to friction force, it is required to set certain
identification torque for the inertia identification to be