WSPC USER INTERFACE Part 1: User Level
40
Power – Displays power in units of KW or HP.
Volume – Displays volume in units of KCF, Feet3, Gallons (US), Liters, M3,
and KM3.
Figure 4.2 User Profiles Window
8. Under “Communication Port” the settings that control communication between
the WS Controller and the WSPC software can be viewed and modified as
necessary. All four must be set properly for the programs to communicate.
The following communication parameters can be adjusted from the User
Profiles window:
Modbus Address – displays the modbus communication ID. The default
modbus ID value is 1 in the WS Controller, but is adjustable.
Com Port – This is the PC’s communication transmission channel through
which data is passed to and from the computer.
Baud Rate The communication speed in bits per second between the WS
Controller and the PC interface. RS232 communications of the WS Controller
is always 38400 Baud. RS485 is 19200 Baud by default, but is adjustable.
Parity – The method used for checking the accuracy of the flow of data
between the computer and communication devices. The parity setting helps
to determine if a transmission error has occurred between devices. RS232
communications of the WS Controller is always “None.” RS485
communication is “Even” by default, but is adjustable.