Part 2: Administrator Level  WSPC USER INTERFACE 
67 
Modulating Mode – Sets the maximum Unload pressure limit for the compressor 
when the machine is operated in Modulating mode. 
6.5.6  Disable Warning Reset 
Current versions of WS Controllers reset warnings whenever the start or stop 
button is pressed on the keypad.  The administrator may disable this feature, and 
require all warnings to be reset by WSPC only.  Refer to Figure 6.10. 
1.  Select the “Start Button” check box to disable reset by the start button. 
2.  Select the “Stop Button” check box to disable reset by the stop button. 
6.5.7 Assigning Digital Inputs  
To make adjustments at the “Admin” Display (Refer to Figure 6.11) : 
1. Click    at the WSPC to connect communication between the 
computer and the WS Controller.  Connection must be enabled before 
adjustments can be made at the Admin display. 
2. Press   (Stop) at the controller to stop the compressor operation.  The 
compressor must be stopped before adjustments can be made at the 
Admin display. 
3.  Click on the drop-down arrow at the right of the row containing the name 
of the function to be reassigned.    
4.  In the drop-down list, select the input to assign to the corresponding 
function.  The new assignment will become active a few seconds after 
entry. 
Figure 6.11  Administrator Adjustments 
 
Click Connect to 
enable Admin 
Adjustments 
Click drop-
down arrow to 
select input 
assignment 
Analog Signal 
Zero Trims for 
calibration 
adjustments