6.5.1 Signal Address Function
Refer to Figure 6.10. The left section contains a list of controller functions, and
allows selection of signals to operate the function. This allows special field
setups for special applications.
General Fault – Generates an Option Input Fault when on.
General Warning – Generates User Option Warning when on.
General Runtime Fault – Generates an Option Input Run Fault when on. This
fault is enabled a few seconds after the compressor starts.
General Runtime Warning – Generates a User Option Warning when on. This
warning is enabled a few seconds after the compressor starts.
Remote Operate – Operates the compressor when on.
Remote Master – Uses Remote inputs when on.
Remote Unload – Forces the compressor to unload when on. Refer to the
Sequencing manual for details on using the remote inputs.
Dryer Warning – Generates Dryer Warning when on.
Dryer Fault – Generates Dryer Fault when on.
Phase Monitor Fault – Generates Phase Monitor Fault when on.
Water Pressure Fault – Generates Water Pressure Fault when on.
Factory-Defined A through E – Operates the factory defined relay when on.
Actual relay assignments are shown, and depend on compressor model.
6.5.2 Digital Input Options (drop-down arrows)
The following options may be selected for a Digital Input by clicking on the
associated drop-down arrow (refer to Figure 6.10):
ON – Activates the function continuously. The input signal is ON.
Off – Deactivates the function. The input signal is OFF.
Running – Activates the function when the Compressor is running.
Din 7, 8, 9, 4 ON – Activates the function when the input signal at the respective
input (7, 8, 9, or 4) is ON. The list of available inputs varies with models.
Din 7, 8, 9, 4 OFF – Activates the function when the input signal at the respective
input (7, 8, 9, or 4) is OFF. The list of available inputs varies with models.
MB Remote ON – Activates the function when the Modbus Remote signal is ON.
MB Timer 1, 2, 3 ON – Activates the function when the respective Modbus Timer
signal (1, 2, 3) is ON.
MB Remote OFF – Activates the function when the Modbus Remote signal is
OFF.