Part 1: User Level  WSPC USER INTERFACE 
27 
Mode – displays the Operating Mode of each compressor in the sequence.  The 
mode is the manner in which the machine’s operation is being controlled.  When 
running and operating normally, a compressor’s operating mode will be either 
“Manual” or “Automatic” as selected by the user.  Other modes are “Stopped” 
when the machine’s operation has been stopped and “Faulted” when a fault has 
occurred. 
Hours – displays the sequence hours of a particular compressor.  Sequence 
hours are the number of hours set for a machine to run in sequence.  This 
parameter can be adjusted at the Adjustments Display to assign the compressor 
to run in a specific order in the sequence system.  When the operating mode is 
set to Automatic, the machine with the lowest number of sequence hours will be 
the next to start and the machine with the highest number of sequence hours will 
be the next to stop. 
PSI  – displays the output pressure of the related compressor.  This may be 
displayed as BAR or Kpa depending on user profile preferences. This 
measurement is taken at the P2 pressure transducer of the compressor and may 
be a different value than the overall system pressure.   
ACFM – shows the capacity of the specific compressor.  Capacity is the volume 
of air in cubic feet per minute (cfm) being delivered by the compressor. 
Remote – indicates whether the compressor operation is being controlled 
remotely (including sequencing control) or by the local controller only.   
Service – displays “Yes” when the compressor is in need of service.  This 
indication is accompanied by either a service reminder or warning message to 
inform the user of the nature of the service required. 
Refer to the WS Controller Sequencing and Protocol Manual for details on 
operating compressors in sequence. 
3.8  ADJUSTMENTS DISPLAY  
Both the compressor control parameters and sequencing parameters can be 
edited at the Adjustments display of the WSPC User Interface.  See Figure 3.12.  
At this display the user can view the current settings of the machine control 
parameters and make adjustments as necessary.  Changes to the control 
parameters will be reflected at the WS Controller located on the compressor.