136
Parameters
SG25CX-
P2
(5)
SG30CX-
P2
(5)
SG33CX-
P2
(5)
SG36CX-
P2
(5)
SG40CX-
P2
(5)
SG50CX-
P2
(5)
Degree of
protection
IP66
Corrosion C5
Operating
ambient
temperature
range
-30 to 60
Allowable
relative hu-
midity range
(non-
condensing)
0 100 %
Cooling
method
Smart forced air cooling
Max. oper-
ating
altitude
4000 m
Display LED, Bluetooth+APP
Communi-
cation
RS485 / WLAN / Optional: Ethernet
DC connec-
tion type
EVO2 (Max. 6 mm² )
AC connec-
tion type
OT terminal (16~35 mm²)
OT or DT
terminal
(35~50
mm²)
AC Cable
specification
Outside diameter 18~38mm
Grid
Support
Q at night function, LVRT, HVRT,active & reactive power control and power
ramp rate control
Note(5):For Latin America.
Note(6):
The voltage difference between MPPTs should be less than 80 V.