108
Step 5 Set Auto Frequency Point Setting to Disable, and modify the frequency point for Inverter 1
by referring to " Check Device Information".
Step 6 Complete layout settings for the other inverters by referring to Steps 2 to 4 specified in this
section.
Each time you are about to carry out layout setting, turn off the DC and AC
switches of the inverters that have not been set. Besides, set different frequency
points for different inverters respectively, with the set values going from high to
low. For instance, the frequency point set for Inverter 1 is 490 kHz, the frequency
set for Inverter 2 is 460 kHz, and so on.
- - End
7.7.4.3 Optimizer Information
If the plant is equipped with optimizers, you will see an icon
in the lower right corner of
the plant’s picture on the Monitoring screen. Tap this plant, and choose Layout at the top of
the screen to view detailed information.
7.7.4.4 View Layout
View Optimizer Layout
Tap
at the upper left of the screen. You can choose Physical Layout or Logical Layout
to check the corresponding layout.
7 iSolarCloud App User Manual