Network Service Provider
Grid Type
SA Power Networks
• TS129-2019: < 10 kW for single-phase
& 30 kW for three-phase
• TS130-2017: > 30 kW & ≤ 200 kW
• TS131-2018: > 200 kW
Horizon Power
• HPC-9DJ-13-0001-2019: ≤ 10 kVA for
single-phase & 30 kVA for three-phase
• HPC-9DJ-13-0002-2019: > 30 kVA &
≤1 MVA
westernpower
EDM#33612889-2019
AusNet Services Basic Micro Embedded Generation:2020
For compliance with AS/NZS 4777.2:2020, please select from Australia A/B/C. Please
contact your electricity grid operator for which region to use.
Step 6 The function of the feed-in limitation is to control the amount of power injected in the grid by
the plant. In some situations, this function is also called as Export limitation or Zero
export. The feed-in limitation function requires the using of Smart Energy Meter. Without the
Smart Energy Meter, the feed-in limitation function will be unavailable.
table 7-2 Description of feed-in limitation parameters
Parameter Default value
Range
Feed-in Limitation Off On / Off
Feed-in Limitation Value 0.00kW
0 ~ Max. AC output power
Feed-in Limitation Ratio 0.0%
0 ~ 100%×Active Overload
Rate*
*The active overload rate of SG30CX-P2 in Germany, Belgium, Austria, Ukraine, and
Denmark is 1, and in other regions is 1.1 (depending on local grid regulations). The active
overload rate of SG25/33/36/40/50CX-P2 is 1.1.
Step 7 After finishing the settings, tap TUNR ON DEVICE at the upper right corner and the device
will be initialized. The App will send start instructions and the device will start and operate.
Step 8 If the inverter is initialized, the App automatically turns to its home page.
- - End