097-58001-01 Revision E – September 2006 TimeProvider TL1 Reference Guide 149
Appendix B Alarms
INPFRQ The specified input
port’s calculated
received frequency is
exceeding the pull-in
range of the local
oscillator. The received
signal’s calculated
frequency alarmed
condition disqualifies
the input as a possible
reference. After
INPFRQ is set, the
alarm clears when the
input frequency is within
the defined pull-in range
limits.
T1 NSA IMMEDNO MNMNNR
INPPHASE The specified input port
has a excessive phase
measurement that is
disqualifies it from being
used.
T1 NSA IMMEDNO MNMNMN
FFOFF Input has exceeded the
Fractional Frequency
Offset threshold.
T1 NSA IMMEDNO MNMNMN
MTIE Input has exceeded at
least one of the MTIE
alarm thresholds.
T1 NSA IMMEDNO MNMNMN
EXDSC Input has had excessive
discontinuities. This is
indicated when there
are more than 3 signal
faults of the same type
within a 5-minute
window. The alarm
clears when the 5-
minute window contains
less than 3 alarms of the
same type.
T1 NSA IMMEDNO MNMNMN
Table B-1. Alarms (Continued)
Alarm ID
or
CONDTYPE
Alarm Condition
Description
AID
Type
Service
Affecting
Error
Delay
Default
Error
Delay
Editable
Alarm Default
Level
SSU PRS SUB

Table of Contents

Other manuals for Symmetricom TimeProvider 1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 1000 and is the answer not in the manual?

Symmetricom TimeProvider 1000 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 1000
CategoryClock
LanguageEnglish

Related product manuals