TECDrive20-EU Series Inverter Function parameters
-92-
Function
code
Name
Description
Default
Modify
P11.04
Overvoltage
stall protective
voltage
110150% (standard bus voltage) (400V)
130%
110150% (standard bus voltage)
(220/230/460V)
120%
P11.05
Current limit
action
The actual increasing ratio is less than the ratio
of output frequency because of the big load
during accelerated running. It is necessary to
take measures to avoid overcurrent fault and the
inverter trips.
During the running of the inverter, this function
will detect the output current and compare it with
the limit level defined in P11.06. If it exceeds the
level, the inverter will run at stable frequency in
accelerated running, or the inverter will derate to
run during the constant running. If it exceeds the
level continuously, the output frequency will keep
on decreasing to the lower limit. If the output
current is detected to be lower than the limit
level, the inverter will accelerate to run.
Output frequency
Output current
Limiting
point
Set
frequency
Acc.
T
T
Constant
speed
Setting range of P11.05:
0: current limit invalid
1: current limit valid
2: current limit is invalid during constant speed
Setting range of P11.05: 0x000x12
Setting range of P11.06: 50.0200.0% (relative
to the percentage of rated current of the inverter)
Setting range of P11.07: 0.0050.00Hz/s
0x01
P11.06
Automatic
current limit
level
G:
160.0%
P11.07
Frequency-
drop rate
during current
limit
10.00
Hz/s
P11.08
Over/under-
load pre-alarm
of motor/
inverter
The output current of the inverter or the motor is
above P11.09 and the lasting time is beyond
P11.10, overload pre-alarm will be output.
0x0000