13 Specific conditions of use and
Functional Safety
13.1 Reliability data
The
MX32v2
controller is certified according to the European standard EN
50271:2010 “Electrical apparatus for the detection and measurement of combustible gases,
toxic gases or oxygen. Requirements and tests for apparatus using software and/or digital
technologies”.
Concerning the requirements relative to the software development process, standard EN
50271 specifies a practical approach in order to satisfy the requirements of EN 61508-3 for
the safety integrity level SIL 1.
The French Notified Body INERIS certified that the
MX32v2
controller conforms to the
necessary requirements and level SIL 1.
1 line version
28.6
60%
7.10.10
-3
1
2 line version
27.1
60%
7.48.10
-3
1
Wheatstone
bridge version
25.3
60%
-3
1
Ti: 12 months
Mean Time to Repair (MTTR): 48 hours
Recommended operating life: 20 years
13.2 Specific Conditions of Use
The safety function of the
MX32v2
is the processing of the signal of the detectors linked to its
input. As soon as a measurement reaches a programmed threshold, an audio and visual alarm
goes off. Simultaneously, the possible corresponding alarm relay(s) is (are) activated,
commanding additional internal or external actions set forth by the user.