7 Maintaining the product
142
4. Once the probe comes back following calibration, link it back up
with the base or the converter.
5. The probe automatically acquires its former configuration data
and continues measuring.
Procedure 2
Here the probe removed from the system is temporarily replaced
with another probe in order to retain measurement data even
during the calibration and adjustment.
1. Register the replacement probe on the base.
2. Configure the replacement probe using the startup wizard. Here
choose the option Use as a replacement.
3. Take replacement probe to the measuring point and wait for
acclimatisation.
4. Press the connect key on both probes, one after the other.
- Replacement is now complete (measurement data is supplied
to the system via the replacement probe).
5. Carry out calibration and adjustment.
6. Register the probe on the base again.
7. Configure the probe using the startup wizard. Here, at Connect
select the option Off and subsequently select the option Use as
a replacement.
8. Take probe back to the measuring point and wait for
acclimatisation.
9. Press the connect key on both probes, one after the other.
- Replacement is now complete (measurement data is supplied
to the system via the original probe once again).
Pos: 172 /TD/Produ kt instand halten/te sto Saveris/Base sic hern @ 0\mod_11894166047 65_79.docx @ 4183 @ 2 @ 1
7.4. Saving data in the Saveris base
✓ Saveris base is started up and connected to the PC.
1. Launch testo startup wizard.
2. Enter IP address of the Saveris base.
3. Click on [Base backup] on the Projects tab.
- Message For backup, the base must be restarted is
displayed. Do not confirm the message.
4. Shut down the Saveris base: in the Info Base menu, press
[Esc] briefly twice.
5. Start up the Saveris base: press and hold down [Esc].
- Menu Select language appears.