EasyManua.ls Logo

Trane Optimus RTHD - Vent Piping Specifications and Thermal Insulation

Trane Optimus RTHD
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RTHD-SVX01L-EN
33
NOTICE
Equipment Damage!
Failure to comply with specifications may result in
capacity reduction, unit damage and/or relief valve
damage.
Do NOT exceed vent piping code specifications!
Relief valve discharge setpoints and capacities rates are
given in . Once the relief valve has opened, it will re-close
when pressure is reduced to a safe level.
Note: Once opened, relief valves may have tendency to
leak and must be replaced.
Figure 17. Relief valve location
Relief
Valves
Evaporator Condenser
W
H
Relief Valves
Evaporator
L
Pressure relief valve discharge capacities will vary with
shell diameter and length and also compressor
displacement. Discharge venting capacity should be
calculated as required by ASHRAE Standard 15-94. Do not
adjust relief valve setting in the field.
Table 6. Pressure relief valve data
Valve
Location -
Size
Dis-
charge
Setpoint
(psi)
Num-
ber of
Valves
Rated
Capacity
per Relief
Valve (lba/
min)
Field
Conn
Pipe
Size
(NPT)
Factory
Shell Side
Conn (in)
Evap - B1
200 1 48 1 1-5/16 - 12
Evap - B2
200 1 48 1 1-5/16 - 12
Evap - B3
200 1 48 1 1-5/16 - 12
Evap - C1
200 1 48 1 1-5/16 - 12
Evap - C2
200 1 48 1 1-5/16 - 12
Evap - D1
200 1 48 1 1-5/16 - 12
Evap - D2
200 1 48 1 1-5/16 - 12
Evap - D3
200 1 48 1 1-5/16 - 12
Evap - D4
200 1 48 1 1-5/16 - 12
Evap - D5
200 1 48 1 1-5/16 - 12
Evap - D6
200 1 48 1 1-5/16 - 12
Evap - E1
200 1 48 1 1-5/16 - 12
Evap - F1
200 1 48 1 1-5/16 - 12
Evap - F2
200 1 48 1 1-5/16 - 12
Evap - G1
200 1 78.8 1-1/4 1-5/8 - 12
Evap - G2
200 1 78.8 1-1/4 1-5/8 - 12
Evap - G3
200 1 78.8 1-1/4 1-5/8 - 12
Cond - B1 200 2 48 1 1-5/16 - 12
Cond - B2 200 2 48 1 1-5/16 - 12
Cond - D1 200 2 48 1 1-5/16 - 12
Cond - D2 200 2 48 1 1-5/16 - 12
Cond - E1 200 2 48 1 1-5/16 - 12
Cond - E2 200 2 48 1 1-5/16 - 12
Cond - E3 200 2 48 1 1-5/16 - 12
Cond - E4 200 2 48 1 1-5/16 - 12
Cond - E5 200 2 48 1 1-5/16 - 12
Cond - F1 200 2 48 1 1-5/16 - 12
Cond - F2 200 2 48 1 1-5/16 - 12
Cond - F3 200 2 48 1 1-5/16 - 12
Cond - G1 200 2 48 1 1-5/16 - 12
Cond - G2 200 2 48 1 1-5/16 - 12
Cond - G3 200 2 48 1 1-5/16 - 12
Comp - B1/
B2
(a)
200 2 78.8 1-1/4 1-5/8 - 12
Comp - C1/
C2
(a)
200 3 78.8 1-1/4 1-5/8 - 12
Comp - D1/
D2/D3
(a)
200 3 78.8 1-1/4 1-5/8 - 12
Comp - E3
(a)
200 3 78.8 1-1/4 1-5/8 - 12
(a)
Only used with isolation valve option
Thermal Insulation
All Optimus™ units are available with optional factory
installed thermal insulation. If the unit is not factory
insulated, install insulation over the areas shaded in Figure
Installation Mechanical

Table of Contents

Other manuals for Trane Optimus RTHD

Related product manuals