22-** Application Functions
Par. No.
#
Parameter description Default value 4-set-up Change
during
opera-
tion
Conver-
sion in-
dex
Type
22-0* Miscellaneous
22-00 External Interlock Delay 0 s All set-ups TRUE 0
Uint1
6
22-2* No-Flow Detection
22-22 Low Speed Detection [0] Disabled All set-ups TRUE - Uint8
22-23 No-Flow Function [0] Off All set-ups TRUE - Uint8
22-24 No-Flow Delay 10 s All set-ups TRUE 0
Uint1
6
22-4* Sleep Mode
22-40 Minimum Run Time 10 s All set-ups TRUE 0
Uint1
6
22-41 Minimum Sleep Time 10 s All set-ups TRUE 0
Uint1
6
22-42 Wake-up Speed [RPM] ExpressionLimit All set-ups TRUE 67
Uint1
6
22-43 Wake-up Speed [Hz] ExpressionLimit All set-ups TRUE -1
Uint1
6
22-44 Wake-up Ref./FB Difference 10 % All set-ups TRUE 0 Int8
22-45 Setpoint Boost 0 % All set-ups TRUE 0 Int8
22-46
Maximum Boost Time 60 s All set-ups TRUE 0
Uint1
6
22-6* Broken Belt Detection
22-60 Broken Belt Function [0] Off All set-ups TRUE - Uint8
22-61 Broken Belt Torque 10 % All set-ups TRUE 0 Uint8
22-62
Broken Belt Delay 10 s All set-ups TRUE 0
Uint1
6
22-7* Short Cycle Protection
22-75 Short Cycle Protection [0] Disabled All set-ups TRUE - Uint8
22-76 Interval between Starts
start_to_start_min_on
_time (P2277)
All set-ups TRUE 0
Uint1
6
22-77 Minimum Run Time 0 s All set-ups TRUE 0
Uint1
6
Parameter Lists
TR200 Programming Guide 279