Main Menu - Frequency Converter Information - Group 15
15-** Drive Information
Parameter group containing frequency converter information such as operating data, hardware configuration
and software versions.
15-0* Operating Data
Parameter group containing operating data e.g. Operating Hours, kWh counters, Power Ups, etc.
15-00 Operating Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the frequency converter has run. The value is
saved when the frequency converter is turned off.
15-01 Running Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the motor has run. Reset the counter in par.
15-07
Reset Running Hours Counter. The value is saved when the fre-
quency converter is turned off.
15-02 kWh Counter
Range: Function:
0 kWh* [0 - 2147483647 kWh] Registering the power consumption of the motor as a mean value over
one hour. Reset the counter in par.15-06
Reset kWh Counter.
15-03 Power Up's
Range: Function:
0 N/A* [0 - 2147483647 N/A] View the number of times the frequency converter has been powered up.
15-04 Over Temp's
Range: Function:
0 N/A* [0 - 65535 N/A] View the number of frequency converter temperature faults which have
occurred.
15-05 Over Volt's
Range: Function:
0 N/A* [0 - 65535 N/A] View the number of frequency converter overvoltages which have oc-
curred.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset
Select
Do not reset
[0] if no reset of the kWh counter is desired.
[1] Reset counter
Select
Reset
[1] and press [OK] to reset the kWh counter to zero (see par.
15-02
kWh Counter).
Note
The reset is carried out by pressing [OK].
Parameter Description
TR200 Programming Guide 161

Table of Contents

Other manuals for Trane TR200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TR200 Series and is the answer not in the manual?

Trane TR200 Series Specifications

General IconGeneral
Input Voltage24 VAC
Frequency Range50/60 Hz
Communication ProtocolsBACnet MS/TP, Modbus RTU
Controller TypeProgrammable
Power Range20 VA
Control MethodPID Control
Enclosure RatingIP20
Operating Temperature32°F to 122°F (0°C to 50°C)
Humidity Range5% to 95% non-condensing
MemoryNon-volatile

Related product manuals