Main Menu - Communications and Options - Group 8
8-** Comm. and Options
Parameter group for configuring communications and options.
8-0* General Settings
General settings for communications and options.
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in par.8-50
Coasting
Select to par.8-56 Preset Reference Select.
[0] * Digital and ctrl.word Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Controlword only Control by using control word only.
8-02 Control Source
Option: Function:
Select the source of the control word: one of two serial interfaces or four
installed options. During initial power-up, the frequency converter auto-
matically sets this parameter to
Option A
[3] if it detects a valid fieldbus
option installed in slot A. If the option is removed, the frequency con-
verter detects a change in the configuration, sets par.8-02
Control
Source back to default setting
FC Port
, and the frequency converter then
trips. If an option is installed after initial power-up, the setting of par.
8-02
Control Source will not change but the frequency converter will trip
and display: Alarm 67
Option Changed
.
[0] None
[1] FC Port
[2] USB Port
[3] * Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can
NOTE: This parameter cannot be adjusted while the motor is running.
Parameter Description
TR200 Programming Guide 125