EasyManua.ls Logo

Trane TR200 Series - Main Menu - Lonworks - Group 11

Trane TR200 Series
295 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Main Menu - LonWorks - Group 11
LonWorks, 11-**
Parameter group for all LonWorks specific parameters.
Parameters related to LonWorks ID.
11-00 Neuron ID
Range: Function:
0 N/A* [0 - 0 N/A] View the Neuron chip's unique Neuron ID number.
11-01 Domain
Range: Function:
0 N/A* [0 - 0 N/A]
11-02 Subnet ID
Range: Function:
0 N/A* [0 - 255 N/A]
11-03 Node ID
Range: Function:
0 N/A* [0 - 255 N/A]
11-10 Drive Profile
Option: Function:
This parameter allows selecting between LONMARK Functional Profiles.
[0] * VSD profile The Trane Profile and the Node Object are common for all profiles.
[1] Pump controller
11-15 LON Warning Word
Range: Function:
0 N/A* [0 - 65535 N/A] This parameter contains the LON specific warnings.
Bit Status
0 Internal fault
1 Internal fault
2 Internal fault
3 Internal fault
4 Internal fault
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9 Changeable types
10 Initialization error
11 Internal communication error
12 Software revision mismatch
13 Bus not active
14 Option not present
15 LON input (nvi/nci) exceeds limits
Parameter Description
134 TR200 Programming Guide

Table of Contents

Other manuals for Trane TR200 Series

Related product manuals