Main Menu - Analog In/Out - Group 6
6-** Analog In/Out
Parameter group for configuration of the analog input and output.
6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The frequency converter is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can freely be
allocated to either voltage (0 - 10 V) or current input (0/4 - 20 mA)
Note
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range: Function:
10 s* [1 - 99 s] Enter the Live Zero Time-out time period. Live Zero Time-out Time is
active for analog inputs, i.e. terminal 53 or terminal 54, used as reference
or feedback sources. If the reference signal value associated with the
selected current input falls below 50% of the value set in par.6-10
Ter-
minal 53 Low Voltage, par.6-12 Terminal 53 Low Current, par.
6-20
Terminal 54 Low Voltage or par.6-22 Terminal 54 Low Current for a
time period longer than the time set in par.6-00
Live Zero Timeout
Time, the function selected in par.6-01 Live Zero Timeout Function will
be activated.
Parameter Description
114 TR200 Programming Guide