6-01 Live Zero Timeout Function
Option: Function:
Select the time-out function. The function set in par.6-01
Live Zero Time-
out Function will be activated if the input signal on terminal 53 or 54 is
below 50% of the value in par.6-10
Terminal 53 Low Voltage, par.
6-12
Terminal 53 Low Current, par.6-20 Terminal 54 Low Voltage or par.
6-22
Terminal 54 Low Current for a time period defined in par.6-00 Live
Zero Timeout Time. If several time-outs occur simultaneously, the fre-
quency converter prioritises the time-out functions as follows:
1. par.6-01
Live Zero Timeout Function
2. par.8-04
Control Timeout Function
The output frequency of the frequency converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
[0] * Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
Parameter Description
TR200 Programming Guide 115