6-61 Terminal X30/8 Min. Scale
Range: Function:
0.00 %* [0.00 - 200.00 %] Scales the minimum output of the selected analog signal on terminal
X30/8. Scale the minimum value as a percentage of the maximum signal
value, i.e. 0 mA (or 0 Hz) is desired at 25% of the maximum output value
and 25% is programmed. The value can never be higher than the corre-
sponding setting in par.6-62
Terminal X30/8 Max. Scale if value is below
100%.
This parameter is active when option module MCB 101 is mounted in the
frequency converter.
6-62 Terminal X30/8 Max. Scale
Range: Function:
100.00
%*
[0.00 - 200.00 %] Scales the maximum output of the selected analog signal on terminal
X30/8. Scale the value to the desired maximum value of the current signal
output. Scale the output to give a lower current than 20 mA at full scale
or 20 mA at an output below 100% of the maximum signal value. If 20
mA is the desired output current at a value between 0 - 100% of the ful-
scale output, program the percentage value in the parameter, i.e. 50% =
20 mA. If a current between 4 and 20 mA is desired at maximum output
(100%), calculate the percentage value as follows:
20
mA
/
desired
maximum
current
× 100 %
i
.
e
. 10
mA
:
20
mA
10
mA
× 100% =200%
6-63 Terminal X30/8 Output Bus Control
Range: Function:
0.00 %* [0.00 - 100.00 %] Contains the value to apply to the output terminal, when it is configured
as [Bus Controlled].
6-64 Terminal X30/8 Output Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00 %] Contains the value to apply to the output terminal, when it is configured
as [Bus Controlled Timeout] and time-out is detected.
Parameter Description
124 TR200 Programming Guide