8-4* Telegram Selection
8-40 Telegram Selection
Option: Function:
Enables use of freely configurable telegrams or standard telegrams for
the FC port.
[1] * Standard telegram 1
[101] PPO 1
[102] PPO 2
[103] PPO 3
[104] PPO 4
[105] PPO 5
[106] PPO 6
[107] PPO 7
[108] PPO 8
[200] Custom telegram 1
8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus merging.
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input)
and/or via the bus.
[0] Digital input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or fieldbus
option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port,
AND additionally via one of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR
via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via
the fieldbus.
[0] Digital input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or fieldbus
option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port,
AND additionally via one of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR
via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.