8-53 Start Select
Option: Function:
Select control of the frequency converter start function via the terminals
(digital input) and/or via the fieldbus.
[0] Digital input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or fieldbus
option.
[2] Logic AND Activates Start command via the fieldbus/serial communication port,
AND additionally via one of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial communication port OR
via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.
8-54 Reversing Select
Option: Function:
Select control of the frequency converter reverse function via the termi-
nals (digital input) and/or via the fieldbus.
[0] * Digital input Activates Reverse command via a digital input.
[1] Bus Activates Reverse command via the serial communication port or field-
bus option.
[2] Logic AND Activates Reverse command via the fieldbus/serial communication port,
AND additionally via one of the digital inputs.
[3] Logic OR Activates Reverse command via the fieldbus/serial communication port
OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the termi-
nals (digital input) and/or via the fieldbus.
[0] Digital input Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial communication port or field-
bus option.
[2] Logic AND Activates the set-up selection via the fieldbus/serial communication port,
AND additionally via one of the digital inputs.
[3] * Logic OR Activate the set-up selection via the fieldbus/serial communication port
OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter Preset Reference selection via
the terminals (digital input) and/or via the fieldbus.
[0] Digital input Activates Preset Reference selection via a digital input.
Parameter Description