[1] Bus Activates Preset Reference selection via the serial communication port
or fieldbus option.
[2] Logic AND Activates Preset Reference selection via the fieldbus/serial communica-
tion port, AND additionally via one of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the fieldbus/serial commu-
nication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.
8-7* BACnet
BACnet configuration
8-70 BACnet Device Instance
Range: Function:
1 N/A* [0 - 4194304 N/A] Enter a unique ID number for the BACnet device.
NOTE: This parameter is active only when par.8-30
Protocol is set to [9]
Drive Option
.
8-72 MS/TP Max Masters
Range: Function:
127 N/
A*
[0 - 127 N/A] Define the address of the master which holds the highest address in this
network. Decreasing this value optimizes polling for the token.
NOTE: This parameter is active only when par.8-30
Protocol is set to [9]
Option
.
8-73 MS/TP Max Info Frames
Range: Function:
1 N/A* [1 - 65534 N/A] Define how many info/data frames the device is allowed to send while
holding the token.
NOTE: This parameter is active only when par.8-30
Protocol is set to [9]
Option
.
8-74 "I-Am" Service
Option: Function:
[0] * Send at power-up
[1] Continuously Choose whether the device should send the "I-Am" service message only
at power-up or continuously with an interval of approx. 1 min.
NOTE: This parameter is active only when par.8-30
Protocol is set to [9]
Option
.
8-75 Initialisation Password
Range: Function:
0 N/A* [0 - 0 N/A] Enter the password needed for execution of Drive Re-initialization from
BACnet.
NOTE: This parameter is active only when par.8-30
Protocol is set to [9]
Drive Option
.
8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus communication via the FC Port.
8-80 Bus Message Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid telegrams detected on the
bus.
Parameter Description
132 TR200 Programming Guide