8-3* FC Port Settings
Parameters for configuring the FC Port.
8-30 Protocol
Option: Function:
Protocol selection for the integrated FC (standard) Port (RS485) on the
control card.
Parameter group 8-7* is only visible when FC Option [9] is chosen.
[0] * FC
Communication according to the FC Protocol as described in the
TR200
Design Guide, RS-485 Installation and Set-up
.
[1] FC MC
Same as
FC
[0] but to be used when downloading SW to the frequency
converter or uploading dll file (covering information regarding parame-
ters available in the frequency converter and their inter-dependencies)
to Trane Drive Utility, TDU.
[2] Modbus RTU Communication according to the Modbus RTU protocol as described in
the
TR200 Design Guide, RS-485 Installation and Set-up
.
[3] Metasys N2 Communication protocol. The N2 software protocol is designed to be
general in nature in order to accommodate the unique properties each
device may have. Please see separate manual
TR200 MetasysMG.
12.NX.YY
.
[4] FLN
[9] FC Option To be used when a gateway is connected to the integrated RS-485 port,
e.g. the BACnet gateway.
Following changes will take place:
-Address for the FC port will be set to 1 and par.8-31
Address, is now
used to set the address for the gateway on the network, e.g. BACnet.
-Baud rate for the Drive port will be set to a fixed value (115.200 Baud)
and par.8-32
Baud Rate, is now used to set the baud rate for the network
port (e.g. BACnet) on the gateway.
[20] LEN
NOTE: Further details can be found in the Metasys manual.
8-31 Address
Range: Function:
1. N/A* [1. - 126. N/A] Enter the address for the FC (standard) port.
Valid range: 1 - 126.
Parameter Description
128 TR200 Programming Guide