8-32 Baud Rate
Option: Function:
Baud rate selection depends on Protocol selection in par.8-30
Protocol.
[0] 2400 Baud
[1] 4800 Baud
[2] * 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option: Function:
Parity and Stop Bits for the protocol par.8-30
Protocol using the FC Port.
For some of the protocols, not all options will be visible. Default depends
on the protocol selected.
[0] * Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range: Function:
10. ms* [5. - 10000. ms] Specify the minimum delay time between receiving a request and trans-
mitting a response. This is used for overcoming modem turnaround
delays.
8-36 Maximum Response Delay
Range: Function:
10001.
ms*
[11. - 10001. ms] Specify the maximum permissible delay time between transmitting a re-
quest and receiving a response. Exceeding this delay time will cause
control word time-out.
8-37 Maximum Inter-Char Delay
Range: Function:
25.00
ms*
[0.00 - 35.00 ms] Specify the maximum permissible time interval between receipt of two
bytes. This parameter activates time-out if transmission is interrupted.
Parameter Description
TR200 Programming Guide 129