46
Table 46-1 Evaporator Fan Performance 3, 4 And 5 Ton
YCD037C, YC
049C, YC 061C
External Static Pressure (Inches of Water) & Motor Power (Bhp)
1
Standard Motor Oversized Motor
Unit
High Speed Low Speed
Tons Model No. CFM ESP BHP ESP BHP ESP BHP
900 0.82 0.28 0.73 0.26
1000 0.77 0.30 0.65 0.28 1.55 0.61
1100 0.70 0.32 0.58 0.30 1.40 0.63
3 1200 0.63 0.34 0.46 0.33 1.23 0.66
YCD037C(L,H) 1300 0.56 0.36 0.32 0.38 1.04 0.69
1400 0.45 0.38 0.84 0.73
1500 0.34 0.40 0.58 0.77
1200 0.83 0.48 0.78 0.35
1300 0.81 0.49 0.72 0.37 1.58 0.74
1400 0.77 0.50 0.64 0.39 1.48 0.77
1500 0.73 0.52 0.56 0.42 1.40 0.80
YCD049C(L,H) 1600 0.68 0.54 0.48 0.44 1.31 0.83
1700 0.62 0.56 0.33 0.49 1.23 0.86
1800 0.56 0.58 1.13 0.90
1900 0.50 0.60 1.05 0.93
2000 0.44 0.62 0.95 0.97
4
1200 0.82 0.45 0.71 0.32 1.55 0.75
1300 0.77 0.46 0.64 0.34 1.49 0.77
1400 0.72 0.48 0.59 0.36 1.43 0.79
1500 0.65 0.49 0.54 0.39 1.35 0.81
YCH049C(L,H) 1600 0.60 0.50 0.44 0.41 1.29 0.83
1700 0.55 0.52 0.34 0.43 1.21 0.86
1800 0.48 0.54 0.20 0.47 1.12 0.90
1900 0.40 0.56 1.03 0.93
2000 0.32 0.58 0.93 0.96
1600 0.76 0.58 0.69 0.46 1.41 0.82
1700 0.71 0.59 0.63 0.48 1.34 0.86
1800 0.66 0.61 0.55 0.50 1.27 0.90
1900 0.60 0.63 0.47 0.52 1.21 0.93
YCD061C(L,H) 2000 0.54 0.66 0.38 0.55 1.15 0.96
2100 0.47 0.69 0.28 0.59 1.06 1.01
2200 0.39 0.71 0.15 0.62 0.96 1.05
2300 0.30 0.73 0.84 1.09
2400 0.22 0.76 0.73 1.13
5
1600 0.78 0.58 0.71 0.46 1.42 0.83
1700 0.74 0.59 0.66 0.48 1.37 0.86
1800 0.69 0.62 0.60 0.50 1.30 0.90
1900 0.64 0.64 0.54 0.52 1.24 0.93
YCH061C(L,H) 2000 0.58 0.66 0.45 0.56 1.17 0.97
2100 0.52 0.68 0.36 0.59 1.10 1.01
2200 0.44 0.70 0.24 0.63 1.04 1.05
2300 0.36 0.73 0.94 1.09
2400 0.26 0.76 0.84 1.13
Fan motor heat (MBH) = 4.39 x Fan Bhp.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be
affected.
NOTES:NOTES:
NOTES:NOTES:
NOTES:
1. Data includes pressure drop due to wet coil and filters.
Denotes either 230 volt or 460 volt.
Performance 3, 4, 5 Ton
Data
High Efficiency