Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Configuration 4 - 51
TYPE: This setting identifies the type of contactor, BAT, LOAD or
NONE that has been installed in the plant. Please be sure that the wiring
for the contactor being configured matches the type chosen here. For
standard GPS configurations using BIC cards, Contactor 1 is wired to
and controls all BATTERY contactors in the plant, while Contactor 2
and Contactor 3 are wired to and control only LOAD contactors.
DISC: This setting configures the plant voltage at which the contactor
will disconnect from the bus.
RECON: This setting configures the plant voltage at which the
contactor will reconnect to the bus. To prevent the contactor from
re-operating when battery voltage increases due to load removal, a
voltage several volts higher than the disconnect voltage is
recommended.
Reserve Configure → Battery Mgmt → Reserve. The parameters associated
with limiting recharge current, disconnecting the batteries due to high
temperature, Battery Test and Reserve Time End Voltage are configured
here.
DES: Allows modification of the default designation.
High Temp Threshold: Sets a temperature at which contactors defined
as battery type contactors will be disconnected from the system. If
Battery Sections have been configured, RPM temperature channels and
LVD contactors linked to different Battery Sections, the contactors will
be independently controlled. One contactor can be linked to several
Battery Sections. The highest temperature of all Battery Sections linked
to the same contactor will be used
Current Limit: Enable / Disable
Current Limit Thld: Sets the total amount of current that will be
allowed to recharge batteries in any Battery Section.
End Volts Per Cell: Sets the minimum voltage the individual battery
cell is intended to discharge to in the system design. Used with the
Reserve Time Predictor algorithm.
Battery Test Class: The only information required for the basic Battery
Test is the type of batteries in the system. Set this field value to
FLOODED or SEALED.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals