Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Feature Descriptions 7 - 20
handshake None, hardware, or software (default: none)
attention prompt A command string that will get the attention of the
connected equipment. This is usually some newline
character sequence. Up to 12 characters are supported.
An escape character is represented as \[, a carriage
return is specified as \r, and a line feed is specified as \n.
A 1/2 second pause can be inserted into the command
string by \, and a 2 second pause can be inserted into a
command string by \.. Up to 12 characters. (default: see
below)
password The password is the keyword used to get into the
connected equipment. It is not visible at the user security
level. The length is up to 20 characters. (default: see
below)
alarms command- This string is used to instruct the connected equipment to
send a report of active alarms. Up to 30 characters.
(default: see below)
header size Number of \r terminated lines in the alarm report header.
The header will be ignored when determining whether the
alarm state has changed or not. (default: see below)
hang-up command This string is sent to the connected equipment to
terminate the connection. Up to 20 characters. (default:
see below)
Defaults When the connected equipment ID configuration parameter is set to
either GALAXY, OMNI, ECS, MCS, RAS, or XCS, the following
parameters are set to the default values listed below:
GALAXY OMNI ECS MCS RAS XCS
baudrate: 9600 9600 9600 1200 1200 1200
databits:8 88777
parity: none none none odd odd odd
stopbits:1 11111
monitor dsr:1 11111
handshake: NO NO NO NO NO NO
attention: \r\,\r”“\r\,\r”“\r\,\r”“\r\,\r”“\r\,\r”“\r\,\r
password: LINEAGE\r”“POLLING\r”“LINEAGE\r
POLLING\r”“LINEAGE\r”“LINEAGE\r
alarms cmd:ALMS\r”“ALMS\r”“ALMS\r”“ALMS\r”“ALMS\r”“ALMS\r
header size:0 96170
hang-up: BYE\r”“BYE\r”“BYE\r”“BYE\r”“BYE\r”“BYE\r

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals