Tyco Electronics Galaxy SC Controller J85501F-1
Appendix A - 2 T1.317 Interface Issue 13 February 2001
* user prompt
** super-user prompt
*** administrator
Login Header At this point the user can enter T1.317 commands. The login header,
which is described below, may be accessed at any time bye entering the
HEADER alias.
:PS1 ; identifies power system controller object
SDE=Mytown Plant ; the site description
SID=12345 ; the site id
DES=AT&T Galaxy Controller; controller description
SWV=2.0.2,2.0.2 ; independent and intelligent controller software versions
DOW=Saturday ; day of the week
DAT=01/01/1994 ; the date
TIM=12:00AM ;the time
.
0 ALARMS ; number of active alarms
.
1 WARNINGS ; number of active warnings
.
:DC1 ; identifies DC plant 1 object
DES=DC Plant 1 ; plant description
VDC=-52.08 V ; plant DC voltage
ADC=635 A ; plant DC current
STT=FLOAT ; plant state|
.
:UNP ; identifies user notepad object
STT=0 ; user notepad state 0:old 1:please read
:SNP ; identifies super-user notepad object
STT=0 ; super-user notepad state 0:old 1:please read
.
* ; command prompt
Objects and
Attributes
The T1.317 standard organizes the power system into objects and
attributes. Objects are resources in the system and are referenced by an
identifier. Examples of objects are DC plant 1 identified as DC1,
rectifiers identified as G01 to G64, and alarms such as the rectifier fail
alarm identified as RFA1. If a command references an object identifier,
such as G01, then that command will be executed on that object.
Each object belongs to a type or class which is also referenced by an
identifier. The type of each object mentioned above is DC plant
identified as DCP, rectifier type identified as REC, and standard alarm
type identified as SDA. If a command references an object type, such as
REC, then the command will be executed on all objects of that type.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals