Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Acceptance Testing 5 - 3
Very Low Voltage - UR3 (VLV)**
High Voltage - HV
Controller - CTLR
User Relay 1 - UR1**
User Relay 2 - UR2**
*RFAT is an alarm test intended for use with non-serial type rectifiers,
connected to the "Enhanced Ferro" RIM (J85501F1 L-32) of a SC
controller ONLY.
** UR1, UR2, and UR3 (VLV) are inhibited if LVD Contactors have
been configured and a Bay Interface Card (BLJ2/3) is not configured in
the system.
The activated alarm relays can be followed during the test by going
straight down the BJT TB2 and TB3 terminal block if the connected
alarm system is not yet processing the power system alarms during
acceptance testing. The default interval for each relay activation during
this test is 60 seconds. Note: Front panel LEDs do not activate during
the alarm test, only the alarm relays whose contacts are accessed on
TB2/3.
Remote Alarm Test An Alarm Test may be performed remotely, in the same manner as that
described for Local Alarm Test, but hardware DIP switch BJH SW204-2
and the remote alarm test software switch in the EasyView path:
Configure → DC Plt → Hardware & Software Config, must also be
enabled. Initiate the test remotely with the EasyView path: Control→
Alarm Test. Follow the status of the test remotely with the EasyView
path: STATUS → ALARM TEST.
High Float
Voltage Alarm
(Serial
Rectifiers)
The high float voltage alarm test can be completed either raising the
system voltage above the threshold set for HFV (High Float Voltage) or
by changing the threshold for this condition to make it active. Raising
the system voltage on a working system is left to the discretion of the
user. Verify the system is in the FLOAT mode and rectifier voltage has
been set to the normal level.
New Installations
(Serial Rectifiers)
1. From the Front Panel follow the path <MENU> → CONFIG →
THRESH and note the settings of both the HV and HFV Float
alarms thresholds. HV must be at least ½ volt higher than HFV.
Press the <ESC> key to return to the Configuration screen. Follow
the path RECT MNGR → PLANT V (FLOAT) (Basic controllers)
or RECT MNGR → RECT OPER → PLANT V (FLOAT)