Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Feature Descriptions 7 - 16
Notes On Calling-out To Pagers
When the phone number type is configured as a pager number, any
alarm may be configured to call-out to the pager number when the alarm
occurs and/or retires. When the alarm call-out condition occurs, the Gal-
axy SC will dial the configured phone number and wait 30 seconds for
10 consecutive seconds of silence. Silence is defined as no rings, beeps,
voice, or other sources of noise. If the pager service provides 10 seconds
of silence, the Galaxy SC will wait the number of seconds configured as
the pager ID delay, to wait out the pager service outgoing message, and
then output the configured pager ID. If the pager service does not pro-
vide 10 seconds of silence while waiting for the pager ID, the Galaxy SC
will not send the pager id and will consider the call-out attempt failed.
Please see the section entitled Call-Out on Alarm Algorithm for a de-
scription of how the Galaxy SC handles failed call-out attempts.
Alarm Call-out
Configuration
Parameters
Once a phone number is configured it can be used as a call-out
destination for an alarm. For most alarms the following parameters may
be configured:
Nag Interval (interval on which to call-out on alarms that remain active)
Range: 15 to 60 minutes (default: 15 minutes)
Notify Delay (minimum number of seconds alarm is active before call-out)
Range: 0 to 540 seconds default: 0
Notify on Occur (call-out when alarm occurs)
Range: 0(no) 1(yes) default: 0(no)
Notify on Retire (call-out when the alarm retires)
Range: 0(no) 1(yes) default: 0(no)
Nag on Occur (call-out periodically if the alarm persists)
Range: 0(no) 1(yes) default: 0(no)
Notification Destination (call-out destination phone numbers)
P1 for phone number 1
P2 for phone number 2
P3 for phone number 3
P4 for phone number 4
Default: none
Note that the alternate phone number cannot be configured as a
destination. This is because the alternate phone number is called
automatically when call-out to any of the phone numbers in the
destination list fails.
Call-Out on Alarm
Algorithm
Assume that an alarm has been configured to call-out on P1 when the
alarm occurs. When it occurs, the Galaxy SC will call out to P1. If P1
cannot be reached, Galaxy SC will then report the alarm to A1 (if

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals