Tyco Electronics Galaxy SC Controller J85501F-1
7 - 51 Feature Descriptions Issue 13 February 2001
Slope Thermal
Compensation
This feature is available only on plants with serial bus rectifiers. Slope
thermal compensation allows the continuous adjustment of battery float
voltage (plant voltage) due to changes in battery temperature,
optimizing the performance of valve regulated batteries. The total
amount of adjustment is calculated at 0.1 times the number cells defined
in the battery plant. The Basic Controller assumes 12/24 cells for 24/48
volt plants. In the Intelligent controller the number of cells per string is
configured by the user. The adjustment to plant voltage per degree
Change Boost Current Threshold
Change Rectifier Status*
Change Rectifier Shunt Voltage configuration
Change Rectifier Float High Voltage Shutdown Threshold
Change Rectifier Boost High Voltage Shutdown Threshold
Change Rectifier Float Set Point
Change Rectifier Boost Set Point
Change Rectifier Boost Current Limit
Change Converter Voltage Set-Point
Change Converter Low Voltage Disconnect Threshold
Change Converter Low Voltage Reconnect Threshold
Enable or disable Converter Low Voltage Disconnect feature
Change Converter Status*
Change Battery High Temperature Threshold
Enable or disable Battery Current Limit
Change Battery Limit Threshold
Change Battery Contactor Status**
Change Battery Disconnect Threshold
Change Battery Reconnect Threshold
Change Very Low Voltage Alarm Threshold and Severity
Change Multiple Rectifier Fail Alarm Threshold and Severity
Change Limited Recharge Current Alarm Threshold and Severity
Change Excess Rectifier Drain Alarm Threshold and Severity
Change Engine Transfer Timeout Alarm Threshold and Severity
Change Reserve Time Low Alarm Threshold and Severity
Change Multiple Converter Fail Alarm Threshold and Severity
Change Battery On Discharge Alarm Threshold and Severity
Change High Voltage Alarm Threshold and Severity
Change High Float Voltage Alarm Threshold and Severity
* The change to Standby or Vacant status is prohibited. The
change to On status is allowed.
** The change to Open status is prohibited. The change to Close
status is allowed.
Table 7-A: Remote Security Via Modem and Auxiliary Ports
Functions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals