Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 T1.317 Objects and Attributes Appendix B - 9
Table B-7: Rectifiers Objects and Attributes
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Rectifier Manager RMN
Identifier IDE TEXT GM1
Description DES TEXT X X X Rectifier Manager 1
Load Share Enable LSE NUMBER X X X 0:disable 1:enable
Float High Voltage Shutdown FSD NUMBER X X X 25-30:27.75 or 50-60:55.50 volts
Boost High Voltage Shutdown BSD NUMBER X X X 26-30:27.75 or 52-60:55.50 volts
Float Set-Point FSP NUMBER X X X 22-28:26.04 or 44-56:52.08 volts
Boost Set-Point BSP NUMBER X X X 22-30:26.04 or 44-60:52.08 volts
Float Current Limit FCL NUMBER X X X 30-110%
Boost Current Limit BCL NUMBER X X X 30-110%
Rectifier Bay RBY
Identifier IDE TEXT RB1 to RB32
Description DES TEXT X X X Rectifier Bay n
Bay Temperature TMP ATTRL
AC Circuit Breaker Alarm ICB ATTRL
Rectifiers REC ATTRL G01 to G64
Rectifier REC
Identifier IDE TEXT G01 to G64
Description DES TEXT X X X Rectifier nn
Rectifier Type TYP TEXT X X X 12 char (default:
UNCONFIGURED)
DC Current (VI, VIR) ADC NUMBER X number A
DC Voltage VDC NUMBER X number V
State STT TEXT X X ON*, OFF, STANDBY*,
VACANT*
Shunt Voltage SHV NUMBER X X X 1-4,294,967,296:50 mV
Capacity CAP NUMBER number A
Temperature TMP NUMBER X number F or C
MAN Type MNT TEXT X X X CC, CO, NONE
Use In Sequence Enable SEQ NUMBER X X X 0:no 1:yes
Output Breaker State OCB TEXT CLOSED, OPEN
Rectifier Fail RFA NUMBER 0:inactive 1:active
AC Fail ACF NUMBER 0:inactive 1:active
Phase or Limited Output PHA NUMBER 0:inactive 1:active
Low Current LCA NUMBER 0:inactive 1:active
Load Share Fuse LSF NUMBER 0:inactive 1:active
Standby or Manual Off MAN NUMBER 0:inactive 1:active
Excess Rectifier Drain ERD NUMBER 0:inactive 1:active
External Transfer Shutdown ETS NUMBER 0:inactive 1:active
Rectifier Incomplete Config RIC NUMBER 0:inactive 1:active
Half Power HPA NUMBER 0:inactive 1:active
ID Conflict DID NUMBER 0:inactive 1:active
Input Breaker State ICB ATTRL
* The user may only set the state to ON, STANDBY, or VACANT