EasyManua.ls Logo

Tyco Galaxy SC Controller - Page 355

Tyco Galaxy SC Controller
413 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tyco Electronics Galaxy SC Controller J85501F-1
Appendix B - 12 T1.317 Objects and Attributes Issue 13 February 2001
Table B-9: Battery Management Objects and Attributes, continued
Related Commands
ATTRIBUTE MNEM TYPE CHA OPE MET CON BACKUP VALUE
Slope Thermal Compensation STC
Identifier IDE TEXT SC1
Description DES TEXT X X X Slope Thermal Comp
State STT NUMBER X X X 0:disable 1:enable
Raise Voltage Enable RVE NUMBER X X X 0:disable 1:enable
Lower Temperature Threshold LTT NUMBER X X X -5-20 ×C or 23-68 ×F
Nominal Temperature Threshold NTT NUMBER X X X 15-30 ×C or 59-86 ×F
Upper Temperature Threshold UTT NUMBER X X X 30-55 ×C or 86-131 ×F
Step Temperature SPT NUMBER X X X 45-85 ×C or 113-185 ×F
Contactor CNT
Identifier IDE TEXT CN1, CN2, or CN3
Description DES TEXT X X X Contactor 1, 2, or 3
Status STT TEXT X NONE, DISCON, CONNECT,
FAILED
Type TYP TEXT X X X NONE, BATTERY, LOAD
Disconnect Threshold DTH NUMBER X X X 20-25:22V or 40-50:44V
Reconnect Threshold RTH NUMBER X X X 22-27:24V or 44-55:48V
Alarm Sub-Objects
Contactor Open Alarm CNO ATTRL CNO1, CNO2, or CNO3
Contactor Failed Alarm CNF ATTRL CNF1, CNF2, or CNF3

Table of Contents